系列代号 Series code
控制电缆control cable………………………………………………………………………………………K
阻燃系列 Flame-retardant series
阻燃A类 Flame-retardant class A…………………………………………………………………………ZA
阻燃B类Flame-retardant class B………………………………………………………………………ZB
阻燃C类Flame-retardant class C…………………………………………………………………………ZC
阻燃D类Flame-retardant class D…………………………………………………………………………ZD
耐火系列 Fire-safe series
阻燃A类耐火flame-retardant class A fire-safe…………………………………………………………ZAN
阻燃B类耐火flame-retardant class B fire-safe…………………………………………………………ZBN
阻燃C类耐火flame-retardant class C fire-safe…………………………………………………………ZCN
阻燃D类耐火flame-retardant class D fire-safe…………………………………………………………ZDN
导体代号Conductor code
铜导体(省略)Copper conductor ( omitted )………………………………………………………………T
绝缘代号Insulation code
聚氯乙烯polyvinyl chloride (PVC)insulated……………………………………………………………V
护套代号1)Sheath code
聚氯乙烯护套 polyvinyl chloride and sheath………………………………………………………………V
聚乙烯护套 polyethylene sheath……………………………………………………………………………Y
铠装代号Amour code
双钢带铠装steel tape armoured ……………………………………………………………………………2
细圆钢丝铠装thin steel-wire armoured ……………………………………………………………………3
外护套代号Outer sheath code
聚氯乙烯外护套 polyvinyl chloride outer sheath …………………………………………………………2
聚乙烯外护套 polyethylene outer sheath ………………………
二:KVV22控制电缆使用特性:
U0/U=450/750 V。
其中:
U0:任一主绝缘导体和“地”(金属屏蔽,金属套或周围介质)之间的电压有效值。
U:多芯电缆(电线)或单芯电缆(电线)系统任一两相导体之间的电压有效值。
2、 导体额定工作温度
电缆导体的最高额定工作温度为70℃。
短路时(最长持续时间不超过5s)电缆导体的最高温度不超过160℃。
3、 敷设环境温度
电缆敷设时的环境温度应不低于0℃,否则需要事先预热。
4、 安装弯曲半径
a) 无铠装层的电缆,应不小于电缆外径的6倍;
b) 有铠装或铜带屏蔽结构的电缆,应不小于电缆外径的12倍;
c) 有屏蔽层结构的软电缆,应不小于电缆外径的6倍。
5、 KVV控制电缆运输和保管要求
电缆盘不允许平放。
运输中严禁从高处扔下装有电缆的电缆盘,严禁机械损伤电缆。
电缆如果需要分段使用,电缆分段后必须用防水封帽将电缆头密封,防止进水。